汇金阀门:专业的调节阀生产厂家。
公称直径(DN)
|
15
|
20
|
25
|
32
|
40
|
50
|
65
|
80
|
100
|
125
|
160
|
200
|
250
|
|||
KVS值(m3/h)
|
1
|
6.3
|
8
|
16
|
20
|
32
|
50
|
80
|
125
|
160
|
280
|
320
|
400
|
|||
节流器压差(∆Pb)的流量范围(m/h)QS(有效压力下的能量范围)
|
0.02Mpa
|
0.1-2
|
0.2-3
|
0.2-4
|
0.4-7
|
0.6-11
|
0.8-16
|
3-28
|
4-40
|
6-63
|
8-80
|
12-125
|
15-150
|
18-180
|
||
0.05Mpa
|
0.2-3
|
0.3-4.5
|
0.3-6
|
0.5-10
|
0.8-16
|
1.2-24
|
4-40
|
6-58
|
9-90
|
12-120
|
18-180
|
12-220
|
18-250
|
|||
Z值
|
0.6
|
0.6
|
0.6
|
0.55
|
0.55
|
0.5
|
0.5
|
0.45
|
0.4
|
0.35
|
0.3
|
0.2
|
0.2
|
|||
******压差∆Pmx(Mpa)
|
Pn16
|
1.6
|
1.6
|
1.6
|
1.6
|
1.6
|
1.6
|
1.6
|
1.6
|
1.5
|
1.5
|
1.2
|
1.0
|
1.0
|
||
Pn40
|
2.0
|
2.0
|
2.0
|
2.0
|
2.0
|
2.0
|
2.0
|
2.0
|
1.5
|
1.5
|
1.2
|
1.0
|
1.0
|
|||
允许泄漏量
(在规定试验条件下)
|
硬密封
|
4×10-4 X阀额定容量(L/H)
|
||||||||||||||
软密封
|
10气泡/分
|
20气泡/分
|
40气泡/分
|
|||||||||||||
执行器有效面积 (cm2)
|
250
|
有效压力 (Mpa) (节流阀压差∆Pb)
|
0.02 0.05
|
允许上下膜室之间有******压差 ∆Pmax (Mpa)
|
0.4
|
设定值偏差
|
±5%
|
控制接头\接头
|
铜管或钢管Ǿ10×1(mm)卡套式管接头 R1/4″
|
执行器有效面积(cm2)
|
32
|
80
|
250
|
630
|
|
阀前压力控制范围
(Mpa)
|
红色弹簧
|
0.3-1.2
|
0.1-0.6
|
0.015-0.15
|
|
黄色弹簧
|
|
0.05-0.3
|
0.01-0.07
|
0.005-0.035
|
|
黑色弹簧
|
0.8-1.6
|
|
|
|
|
适用公称通径DN(mm)
|
15~125
|
15~250
|
|||
保证压力阀正常的工作的最小压差∆Pmin(Mpa)
|
≥0.05
|
≥0.04
|
≥0.01
|
≥0.005
|
|
允许上下膜室之间的******压差∆Pmax(Mpa)
|
2.0
|
1.25
|
0.4
|
0.15
|
|
设定值偏差
|
±8%
|
||||
控制管线\接头
|
铜管或钢管 Ǿ10×1(mm)卡套式管接头R1/4″
|